ARCTIC PROTECTION 95%
Powerful Freeze and Burst Protection for Closed Systems
ARCTIC PROTECTION 95% is a premium propylene glycol-based antifreeze designed to safeguard chilled water, hydronic, and other closed systems from freezing and bursting. Its advanced formulation offers exceptional protection down to -100°F while ensuring safety and compatibility with various systems.
1 gallon size is available in 95% only, for alternative concentrations, colors, and sizes, see AP-5, 55, 275 for customization options and requirements.
Key Features and Benefits:
- Powerful Freeze Protection: Prevents freezing and bursting in extreme cold conditions.
- Highly Concentrated: AP-1 is made only in 95% concentration.
- Corrosion Inhibited: Contains a custom inhibitor package designed for broad protection.
- GRAS Ingredients: Contains generally recognized as safe (GRAS) ingredients.
- Versatile Applications: Suitable for chilled water, hydronic, and other closed systems.
- Leak Detection: Standard blue dye to easy leak detection (colors are customizable, product is blue unless specified).
Part Number; Size
For a custom blend of color or percentage please contact us for a quote, we need the following information: container size (5, 55, 275), quantity in gallons, delivery zip code and color. (blue is standard, clear, green, pink, orange, red, yellow and more are available). **Custom orders not available in 1 gallon containers.
Directions:
- Clean new or lightly corroded systems with Vapco Hydronic System Cleaner (HSC‑1, HSC‑5, HSC‑55) before adding Arctic Protection. Do not use Arctic Protection with galvanized steel.
- For extensively corroded systems, clean with an inhibited acid such as Scale Remover #1 (SR1‑1) or Tankless DeScaler (TDS‑16oz, TDS‑1). Work must be performed by an experienced technician. Complete all necessary replacements and repairs before treatment.
- Choose the protection type:
- Burst protection: Prevents bursting/mechanical damage but does not keep the solution pumpable.
- Freeze protection: Higher glycol level that prevents ice crystal formation at the lowest expected temperature, keeping the fluid pumpable.
- Application guidance: Ice storage, fire sprinkler, and intermittently run hydronic systems may use burst protection. Chilled water and lawn sprinkler systems require freeze protection.
- Using the propylene glycol chart, select the lowest expected ambient temperature, then use a temperature 5°F colder for safety. From that row, note the percentage of Arctic Protection required for your chosen protection type – Freeze or Burst.
- Calculate quantity:
- V = system volume (gal)
- C = required final glycol percentage from the chart (as a decimal, e.g., 40% = 0.40)
- S = glycol strength of the product you’re using (as a decimal, e.g., 95% = 0.95; 50% = 0.50)
- Gallons of Arctic Protection to add = (V x C) ÷ S
- Gallons of DI water to add = V – Arctic Protection to add
- For corrosion protection, maintain a minimum concentration of 35–40% Arctic Protection.
EXAMPLE:
Target glycol = 25 gal × 0.30 = 7.5 gal pure glycol
Product needed = 7.5 ÷ 0.95 = 7.125 gal (typically round to 8 gal for ordering)
DI Water to add = 25 − 7.125 ≈ 17.875 gal
Note: Assumes the system starts empty with water added to reach 200 gallons. If there’s existing fluid, you’ll need to account for its volume and glycol concentration.
Glycol Calculator & Freeze/Burst Chart
Safety Precautions:
- Read Label and SDS: Carefully review the product label and Safety Data Sheet before use.
- Keep Out of Reach: Store out of the reach of children.
- Avoid Mixing: Do not mix with other unknown corrosion inhibiting products.
By following these steps, you can effectively apply ARCTIC PROTECTION to protect your closed system from freezing and bursting.
SDS
⚠️ ARCTIC PROTECTION SDS – DOWNLOAD
1. Identification & Supplier Details
| Product Name |
Arctic Protection |
| Product Number |
AP-1, AP-5, AP-55, AP-275 |
| Brand |
Vapco |
| Recommended Use |
Propylene glycol based antifreeze |
| Supplier |
Vapco Products, Inc. |
| Address |
401 Marshall Road, Valley Park, Missouri 63088, United States |
| Telephone / Fax |
(636) 923-2121 / (636) 923-3002 |
| Emergency Phone |
(800) 255-3924 |
2. Hazard Identification & Composition
| GHS Classification |
Not a hazardous substance or mixture (OSHA 29 CFR 1910.1200, 2024) |
| Label Elements |
None; Not a hazardous substance or mixture |
| Other Hazards |
None known |
| Composition |
Does not contain any hazardous ingredients at or above reportable levels defined by OSHA |
3. Physical & Chemical Properties
| Property |
Value |
| Physical State / Appearance |
Liquid / Clear liquid |
| Color / Odor |
Various / No distinct odor |
| pH |
9.5 – 10.5 |
| Freezing Point |
-76°F (-60°C) |
| Flash Point |
> 200°F (93°C) |
| Auto-ignition Temperature |
700°F (371°C) |
| Solubility |
Completely soluble |
| Relative Density / Vapor Density |
1.00 – 1.10 / 2.6 (Air = 1) |
| Kinematic Viscosity |
45 mPas at 20°C (68°F) |
4. Stability & Reactivity
| Reactivity |
None known |
| Chemical Stability |
Stable under normal conditions of use |
| Conditions to Avoid |
Extremely hot or cold temperatures |
| Incompatible Materials |
None known |
| Hazardous Decomposition |
None known |
5. Toxicological Information
| Acute Toxicity |
Not established |
| Skin Corrosion / Irritation |
Not established |
| Serious Eye Damage |
May cause irritation |
| Carcinogenicity |
Not classified |
| Target Organ Toxicity |
Not classified (Single or Repeated exposure) |
6. First-Aid Measures
| Inhalation |
Remove to fresh air. Keep at rest in a position comfortable for breathing. Get medical attention |
| Skin Contact |
Drench with water for 15 minutes. Remove contaminated clothing. Obtain medical attention if irritation persists |
| Eye Contact |
Rinse with water for 15 minutes. Remove contact lenses if possible. Obtain medical attention if irritation persists |
| Ingestion |
Rinse mouth. Do NOT induce vomiting. Obtain medical attention |
| General Advice |
Never give anything by mouth to an unconscious person. If unwell, seek medical advice and show label |
7. Fire-Fighting & Accidental Release Measures
| Extinguishing Media |
Water spray, fog, CO2, alcohol-resistant foam, dry chemical, or sand |
| Firefighting Equipment |
Wear NIOSH-approved SCBA with full body protective clothing |
| Personal Precautions |
Avoid contact with skin/eyes. Do not breathe vapors/mist. Eliminate ignition sources |
| Cleanup Methods |
Contain spills with dikes or absorbents. Take up liquid spill into absorbent material and transfer to container for disposal |
8. Handling, Storage & PPE
| Safe Handling |
Avoid contact with eyes, skin, and clothing. Wash hands before eating or smoking. Do not breathe vapors |
| Storage Conditions |
Store in original container in a cool, dry, well-ventilated place. Protect from sunlight. Avoid temperatures over 122°F (50°C) |
| Engineering Controls |
Ensure adequate ventilation. Provide eye wash fountains and safety showers in the immediate vicinity |
| Personal Protective Equipment |
Chemical safety goggles, protective gloves, and suitable protective clothing. Use NIOSH SCBA if exposure limits are exceeded |
9. Transport & Regulatory Information
| DOT (US) / IMDG / IATA |
Not dangerous goods |
| US EPA TSCA |
All chemicals are listed or exempt |
10. Disposal & Ecological Information
| Disposal Methods |
Dispose of contents/container in accordance with local, regional, national, and international regulations |
| Biodegradability |
This product is biodegradable |
| Bioaccumulation |
This product is not expected to bioaccumulate |
| Mobility in Soil |
This product is mobile in soil |
11. Disclaimer & Preparation Information
| Disclaimer |
Information is accurate to the best of our knowledge. No assumption of liability for accuracy or completeness. User is responsible for suitability. Manufacturer not responsible for loss/injury from improper use |
| Prepared By |
Jessica Wilson |
| Date Prepared |
2025-03-12 (Version 1.0) |